Accuracy
- Differential Pressure Indication: Approximately 1.5% Mid 50% of Range, 3% at Ends, Window is Plexiglass & Gasketed, Indicator may be Field Adjusted for Approximately ± 1% Accuracy at any Set Point within Range
Adjustment Type
- Captive Clamp Screws
- Factory Set (Pre-Set)
- Set Point Adjustment
Ambient Temperature Range
- -40° to 71° C (-40° to 160° F), Set Point Typically Shifts less than 1% of Range for a 28° C (50° F) Ambient Temperature Change
Applications
- Energy Generation Including Pumps
- Industrial Gas Production
- Pulp & Paper
- Turbines & Compressors
- Water & Wastewater Treatment
Approvals & Certifications
- ATEX Ex Directive (94/9/EC) II 1 G Ex Ia IIC T6 Ga Tamb: -50° to 60° C (-58° to 140° F)
- CE
- CSA C22.2 No. 14, File # E42272
- FM Class 3545
- GOST-R 51330.0, 51330.1, 51330.10 & 51330.14
- Low Voltage Directive (LVD) 2006/95/EC
- PED: 97/23/EC
- UL (C,US) 508
Approvals & Certifications
Deadband
- psi: 0.5 to 3 (kPa: 3.4 to 20.7, Mbar: 34.5 to 206.8)
Electrical Connectors
- 7/8" Hole to 1/2" NPT Female Watertight Conduit Fitting
- One 3/4" NPT
- Screw Terminal
- Two 7/8" Diameter Knockouts
Electrical Contacts
- Gold Contacts, 1 A at 125 Vac Resistive
- Normally Closed
- Normally Open
Electrical Rating
- 1 A at 125 Vac Resistive
- 10 A at 125 Vdc Resistive, Deadband & Minimum Set Point will Increase
- 20 A, 125/250/480 Vac Resistive
- Adjustable Deadband, External Manual Reset, High Ambient, 15 A at 125/250/480 Vac Resistive, Temperatures up to 145° C (250° F)
- Close Deadband, 5 A at 125/250 Vac Resistive
- Vapor Sealed, Fungus Resistant Case,15 A 125/250 Vac Resistive
Enclosure, Body Material
- Gasketed Die Cast Aluminum
Environmental Protection
- Intrinsically Safe
- IP66
- NEMA 4X
- Weathertight
Name Plate, Tag Material
- Stainless Steel, Paper ID Tag & Wire Attachment
Operating Pressure
- psi: -14.7 to 180 (kPa: -101.4 to 1,241, bar: -1 to 12.4)
Process Connection Material
Proof Pressure
- psi: 300 (kPa: 2,068, bar: 20.7)
Repeatability
- Set Point Repeatability: ± 2% of Full Scale
Service
- Oxygen Service Cleaning, Alcohol Cleaning to Remove Residue from the Process Connection
Set Point - Decreasing
- bar: 0.2 to 6.9
- kPa: 20.7 to 689.5
- psid: 3 to 100
Set Point - Increasing
- bar: 0.2 to 6.9
- kPa: 20.7 to 689.5
- psid: 3 to 100
Shock
- Set Point Repeats after 15 G, 10 millisecond Duration
Storage Temperature
- -54° to 71° C (-65° to 160° F)
Switch Type
- DPDT Switch, 10 A at 125/250 Vac Resistive, Deadband & Minimum Set Point will Increase
- One SPDT Switch, May Be Separated up to 100% of Range
System Pressure
- bar: 12.4
- kPa: 1,241
- psi: 180
Vibration
- Set Point Repeats after 2.5 G, 5 to 500 Hz