Accuracy
- Input for Resistance Thermometer & Standard Signals (Measurement Accuracy): ≤ 0.05 to 1% with 250 milliseconds Sampling Time
- Thermocouple Input (Measurement Accuracy): ≤ 0.25% with 250 milliseconds Sampling Time
Ambient Temperature Range
- -5° to 50° C (23° to 122° F)
Approvals & Certifications
- EMC EN 61 326 (Emission - Class B, Immunity - to Industrial Requirements)
- UL 94
Approvals & Certifications
- Electrical Safety: EN 61 010, Part 1 Overvoltage Category III, Pollution Degree 2
Circuit Protection
- Solid-state Relay: Varistor
Communication
- Baud Rate: 9,600, 19,200, 38,400 - Interface (COM1)
- Ethernet - Interface (COM2)
- Interface Typical: PC-interface - COM1
- Interface Typical: RS-422/RS-485 - COM1 - Interface (COM1)
- Profibus DP - Interface (COM2)
- Protocol: Modbus - Interface (COM1)
- RS-232 - Interface (COM1)
- TCP/IP Protocols - Interface (COM2)
Current
- Input for Resistance Thermometer (Measuring Current): 250 µA
- Measurement Circuit Monitoring (Sensor): 0-20 mA
- Measurement Circuit Monitoring (Sensor): 4-20 mA
Display
- 5" Colour Graphics Display with 27 Colours
Electrical Connectors
- Connection Circuit: 2-Wire - Input for Resistance Thermometer
- Connection Circuit: 3-Wire - Input for Resistance Thermometer
- Plug-in Screw Terminals Conductor Cross-section, Maximum
Electrical Contacts
- Relay: Changeover Contact
- Solid-state Relay: 1 A at 230 V
Enclosure, Body Material
- Front Bezel: Plastic to UL94 V0 144 mm x 130 mm
- Metal
Humidity
- ≤ 75% Relative Humidity Annual Mean, Non-Condensing
Isolation
- Electrical Isolation: 2,300 Vac
- Electrical Isolation: 42 Vac
- Electrical Isolation: 60 Vdc
Load Resistance
- Current: ≤ 450 ohms
- Voltage: ≥ 500 ohms
Measuring Range
- Input for Standard Signals (Heat Current): 0-50 mA AC
- Input for Standard Signals (Potentiometer): 100 to 10,000 ohms
- Input for Standard Signals: 0-20 mA, Voltage Drop ≤ 1 V
- Input for Standard Signals: -10-10 V
- Input for Standard Signals: 4-20 mA, Voltage Drop ≤ 1 V
Mounting
- Mounting Depth: 170 mm
- Panel Mounting as Per ISO 43 700
Output
- 0-10 V
- 2 to 10 V
- 4-20 mA
- Logic: 0-20 mA
- Logic: 0-22 V
- Logic: 0-30 mA
- Logic: 0-5 V
Relay Output
- Contact Rating: 3 A at 250 Vac Resistive Load
Resistance
- Input for Resistance Thermometer (Sensor Lead Resistance): Maximum
- Input for Standard Signals: > 100 KiloOhms
Resolution
- A/D Converter (Dynamic Resolution): 0 to 16-bits - Controller
- Color Screen: 320 x 240 Pixels
Response Time
- Minimum 0 to 500 milliseconds - Interface (COM1)
RTD Type
- Cu50 - Input for Resistance Thermometer
- KTY11-6 - Input for Resistance Thermometer
- Ni100 (DIN 43 760) - Input for Resistance Thermometer
- Pt100 (EN 60 751) - Input for Resistance Thermometer
- Pt1000 (EN 60 751) - Input for Resistance Thermometer
- Pt50 (EN 60 751) - Input for Resistance Thermometer
- Pt500 (EN 60 751) - Input for Resistance Thermometer
- PtK9 - Input for Resistance Thermometer
Sample Rate
- 250 milliseconds [50 milliseconds, 150 milliseconds, 250 milliseconds (Configurable)]
Sensor, Probe Type
- B Thermocouple
- C Thermocouple
- D Thermocouple
- E Thermocouple
- J Thermocouple
- K Thermocouple
- L Thermocouple
- N Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
- U Thermocouple
Size
- Screen Diagonal: 5" (12.7 cm)
Storage Temperature
- -40° to 70° C (-40° to 158° F)
Supply Voltage
- 20-30 Vac/Vdc
- For 2-Wire Transmitter: 22 V at 30 mA
- Switchmode PSU: 110-240 Vac, -15 to 10% at 48 to 63 Hz
Temperature Effect
- Input for Resistance Thermometer (Ambient Temperature Error): 50 ppm / °C
- Input for Standard Signals & Thermocouple Input (Ambient Temperature Error): 100 ppm / °C
Temperature Range
- Input for Resistance Thermometer: -200° to 850° C (-328° to 1,562° F)
- Thermocouple Input: -200° to 2,495° C (-328° to 4,523° F)
Voltage
- Measurement Circuit Monitoring (Sensor): 0-10 V
- Measurement Circuit Monitoring (Sensor): 2 to 10 V