Adjustment Type
- Factory Set (Pre-Set)
- Field Adjustable
Ambient Temperature Range
- -18° to 71° C (0° to 160° F)
Approvals & Certifications
Deadband, Approximate
- bar: 0.8 to 1.8
- kPa: 82.73 to 179.26
- psig: 12 to 26
Electrical Connectors
- 1/2" NPT Female Conduit Connection
- 7/8" Diameter Knockout
Electrical Rating
- 15 A 125/250/480 Vac Resistive, 24-30 Vdc, 2 A Resistive & 1 A Inductive, 125 Vdc, 0.5 A Resistive, 0.03 Inductive
Enclosure, Body Material
- Die Cast Aluminum, Epoxy Coated
Process Connection Material
Proof Pressure
- bar: 68.9
- kPa: 6,895
- psig: 1000
Set Point - Decreasing
- bar: 1.4 to 13.8
- kPa: 13.78 to 1,378
- psi: 20 to 200
Set Point - Increasing
- bar: 1.4 to 13.8
- kPa: 13.78 to 1,378
- psig: 20 to 200
Shock
- Set Point Repeats after 15 G, 10 millisecond Duration
Standard Features
- Tamper-Resistant Set Point "Lock"
System Pressure
- bar: 1.4 to 34.5
- bar: 34.5
- kPa: 13.78 to 3,447
- kPa: 3,447
- psig: 20 to 500
- psig: 500
Vibration
- Set Point Repeats after 2.5 G, 5 to 500 Hz