Eclipse EN/EG On/Off Valve Monitor

Brand: Metso

StoneL’s Eclipse features dual solid state sensors with optional communications neatly integrated into a sealed module. 

The function module and trigger/indicator attach quickly and conveniently to standard VDI/VDE 3845 (NAMUR) actuator accessory mounting pads. 

The Eclipse series is available in nonincendive and intrinsically safe versions (EN) for hazardous areas and in a general-purpose completely sealed microconnector version (EG).
Features
  • No moving mating parts assure long life and trouble-free operation
  • Red/green visual indicator boldly displays valve status, and coordinates with red/green LEDs
  • Direct attachment to ISO/NAMUR mounting pads with simple mounting kit (sold separately)
  • High intensity red and green LEDs indicate electronic switch status to confirm electrical operation
  • Sensor triggers are adjustable in 3.5 degree increments through 360 degrees for precision and flexibility
  • Submersible and capable of high pressure washdown, Eclipse sensors and electronics are fully sealed to eliminate hazard threat and corrosion problems

Specifications

Brand

Approvals & Certifications

  • CEC
  • IEC
  • NAMUR
  • NEC
  • VDI/VDE 3845

Communication

  • AS-Interface
  • Baud Rate: 125, 250, 500 Kbps - DeviceNet (92)
  • DeviceNet

Conduit Connection

  • 1/2" NPT Female
  • M20 Female
  • Micro Connector (5-Pin, 4-Pin)
  • Mini Connector (5-Pin, 4-Pin, 3-Pin)

Configuration

  • 4-20 mA Auxiliary Analog Input - DeviceNet (92)
  • Auxiliary Discrete Input - AS-Interface (96), AS-Interface VCT with Extended Addressing (97)
  • Discrete Input - DeviceNet (92), AS-Interface (96), AS-Interface VCT with Extended Addressing (97)
  • NAMUR Sensor (EN 60947-5-6, I.S) - NAMUR Sensor
  • Power Output - DeviceNet (92), AS-Interface (96), AS-Interface VCT with Extended Addressing (97)
  • Solid State Sensor - Stainless Steel Switching Sensor
  • Wire Terminations - Stainless Steel Switching Sensor, NAMUR Sensor

Connection Material

  • Quick Connectors: Stainless Steel

Current

  • Maximum
  • Minimum on Current: 2 mA - Stainless Steel Switching Sensor
  • Target Off I> 3 mA - NAMUR Sensor
  • Target on I< 1 mA - NAMUR Sensor

Electrical Connectors

  • Terminal Strip

Electrical Contacts

  • Normally Closed
  • Normally Open

Electrical Rating

  • Maximum

Enclosure, Body Material

  • Lexan® Polycarbonate

Environmental Protection

  • IP66
  • IP67
  • NEMA 4
  • NEMA 4X
  • NEMA 6

Indication

  • Visual: Red/Green LED's

Input

  • Auxiliary: 24 Vdc at 2 mA (Self-Powered) - AS-Interface (96), AS-Interface VCT with Extended Addressing (97)

Materials of Construction

  • Drum Components: Polycarbonate
  • Fasteners, Triggers & Coupling: Stainless Steel

Operation

  • Normally Closed (Solid State) - NAMUR Sensor

Output

  • 2 W at 24 Vdc - AS-Interface VCT with Extended Addressing (97)
  • 21-26 Vdc - AS-Interface (96), AS-Interface VCT with Extended Addressing (97)
  • 24 Vdc (Input Voltage Ranging from 10-24 Vdc) - DeviceNet (92)
  • 4 W at 24 Vdc Both Outputs Combined - DeviceNet (92), AS-Interface (96)

Rotation

  • 0° to 90°

Temperature Range

  • -40° to 80° C (-40° to 176° F)

Voltage

  • 24-125 Vac - Stainless Steel Switching Sensor
  • 5-25 Vdc - NAMUR Sensor
  • 8-125 Vdc - Stainless Steel Switching Sensor

Voltage Drop

  • 7.5 V at 100 mA - Maximum
  • Maximum

show more