Appleton™ ATX™ D Series Pre-Drilled Control Stations
Brand: AppletonAppleton™ flameproof ATX™ D Series pre-drilled control stations provide safe control of equipment in classified hazardous locations. They are empty enclosures pre-drilled to accommodate a variety of push buttons, pilot lights, ammeters and limit switches. They are ideal for the control of electrical equipment at power plants, chemical and petrochemical plants, petroleum refineries, pulp and paper processing plants and various industrial applications.
FeaturesSpecifications
Brand
Approvals & Certifications
- Zone 1 & 2 - 21 & 22, Ex II 2 GD, IP66, IK09, IK10
Ex D IIB Ambient Temperature
- -40° to +55° C (-40° to +131° F)
Ex D IIB Surface Temperature
- T95° C (T203° F)
Ex D IIB Temperature Class
- T6 for Ta = +40° C (+104° F), T5 for Ta = +55° C (+131° F)
Ex D IIC Ambient Temperature
- BR1d, BR2d & CF2B: -40° to +55° C (-40° to +131° F)
Ex D IIC Surface Temperature
- BR1d: T95° C (T203° F). BR2d: T80° C (T176° F). CF2B: T95° C (T203° F)
Ex D IIC Temperature Class
- BR1d: T6 for Ta = +40° C (+104° F), T5 for Ta = +55° C (+131° F). BR2d: T6. CF2B: T6 for Ta ≤ +40° C (+104° F), T5 for +40 (+104° F) °C < Ta ≤ +55° C (+131° F)
Standard Materials & Finishes
- BR1d, BR2d & CF2D: Gray Painted Marine Grade Aluminum Alloy. CF2B: Gray Painted Cast Iron