Ambient Temperature Range
- Standard Version: -40° to +65° C (-40° to +149° F) Emergency Version: -20° to +55° C (-4° to +131° F)
Electrical
- 120-277 Vac, 50/60 Hz, 125-300 Vdc or 347-480 Vac
Lumens to Watts
- (2 feet) 4390 Lumens is equivalent to 2 x 32 W T8 Lamps, (4 feet) 7650 Lumens is equivalent to 3 x 32 W T8 Lamps
NEC/CEC Certifications & Compliances
- Class I, Division 2, Groups A, B, C, D, Class II, Division 2, Groups F, G, Class III, Class I, Zone 2, Group IIC, Class II, Zone 22, Typical 3R, 4, 4X, IP66, Simultaneous Exposure, Suitable for use in Wet Locations, Marine Outside Typical (Salt Water) -
Options
- Factory Installed or Individual Brackets, Safety Cable, 1/2" or 3/4" NPT Threads, Clear Polycarbonate Lens or Diffused Lens, Wirenuts or Screw Terminal Blocks, Emergency Battery Backup
Standard Materials & Finishes
- Housing is Copperfree (4/10 of 1% Max.) Aluminum with Electrostatically Applied Baked Gray Epoxy-clad Finish. Thermal Shock- & Impact-Resistant Polycarbonate Lens. Silicone Rubber Gasket, Mechanically Secured. Stainless Steel Bolts, Aluminum Close Up Pl